Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: RC10 rowsPage 3 of 5
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
RCRC-35#400045284,000RC-35classroom
RCRC-35#5004540500RC-35classroom
RCRC-35#63456363RC-35classroom
RCRC-35#800045268,000RC-35classroom
RCRC-40#100050401,000RC-40office open
RCRC-40#1255058125RC-40office open
RCRC-40#200050362,000RC-40office open
RCRC-40#2505051250RC-40office open
RCRC-40#400050334,000RC-40office open
RCRC-40#5005045500RC-40office open