Noise Criteria Curves: RC

RC-50#1000 to RC-50#8000

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: RC8 rowsPage 5 of 5
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
RCRC-50#100060501,000RC-50retail
RCRC-50#1256066125RC-50retail
RCRC-50#200060462,000RC-50retail
RCRC-50#2506059250RC-50retail
RCRC-50#400060434,000RC-50retail
RCRC-50#5006054500RC-50retail
RCRC-50#63607563RC-50retail
RCRC-50#800060418,000RC-50retail