Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Noise Criteria Curves: RC

RC-30#2000 to RC-35#250

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: RC10 rowsPage 2 of 5
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
RCRC-30#200040262,000RC-30office private
RCRC-30#2504042250RC-30office private
RCRC-30#400040234,000RC-30office private
RCRC-30#5004035500RC-30office private
RCRC-30#63405963RC-30office private
RCRC-30#800040218,000RC-30office private
RCRC-35#100045351,000RC-35classroom
RCRC-35#1254554125RC-35classroom
RCRC-35#200045312,000RC-35classroom
RCRC-35#2504547250RC-35classroom

What else is in Engineering Database