Motor Starting Methods: starting_power_factor

IEEE Std 3002.7-2018 motor starting study data: critical voltage limits during motor starting, autotransformer tap current and torque percentages, locked-rotor starting power factor by motor rating, reduced-voltage starter method comparison (voltage/current/torque), and net acceleration torque vs speed profile.

Electrical Engineeringcategory: starting_power_factor3 rows
categoryparameter namedescriptionpower factor (dimensionless)standard
starting_power_factorRating_1000HPLocked-rotor starting power factor for motors rated 1000 HP (750 kW)0.15IEEE Std 3002.7-2018
starting_power_factorRating_100HPLocked-rotor starting power factor for motors rated 100 HP (75 kW)0.3IEEE Std 3002.7-2018
starting_power_factorRating_2500_to_7000HPLocked-rotor starting power factor for motors rated 2500 to 7000 HP (1875 to 5250 kW)0.13IEEE Std 3002.7-2018