Motor Starting Methods: accel_torque_vs_speed
IEEE Std 3002.7-2018 motor starting study data: critical voltage limits during motor starting, autotransformer tap current and torque percentages, locked-rotor starting power factor by motor rating, reduced-voltage starter method comparison (voltage/current/torque), and net acceleration torque vs speed profile.
| category | parameter name | description | standard | torque pct (%) | value lb ft (lb-ft) |
|---|---|---|---|---|---|
| accel_torque_vs_speed | Speed_0pct | Net acceleration torque at 0% speed: Tmotor=100% Tload=30% Tnet=77.5% | IEEE Std 3002.7-2018 | 77.5 | 2,260 |
| accel_torque_vs_speed | Speed_25pct | Net acceleration torque at 25% speed: Tmotor=120% Tload=35% Tnet=100% | IEEE Std 3002.7-2018 | 100 | 2,917 |
| accel_torque_vs_speed | Speed_50pct | Net acceleration torque at 50% speed: Tmotor=160% Tload=45% Tnet=120% | IEEE Std 3002.7-2018 | 120 | 3,500 |