Motor Starting Methods: critical_voltage_limit
IEEE Std 3002.7-2018 motor starting study data: critical voltage limits during motor starting, autotransformer tap current and torque percentages, locked-rotor starting power factor by motor rating, reduced-voltage starter method comparison (voltage/current/torque), and net acceleration torque vs speed profile.
| category | parameter name | description | standard | value max pct (%) | value min pct (%) |
|---|---|---|---|---|---|
| critical_voltage_limit | AC_contactor_pickup | Minimum voltage for AC contactor pick-up per standard | IEEE Std 3002.7-2018 | — | 85 |
| critical_voltage_limit | Contactor_hold_in | Minimum voltage for contactor hold-in (average of contactors in use) | IEEE Std 3002.7-2018 | 70 | 60 |
| critical_voltage_limit | DC_contactor_pickup | Minimum voltage for DC contactor pick-up per standard | IEEE Std 3002.7-2018 | — | 80 |