Lighting Load Densities: gymnasium_exercise to healthcare_recovery_room
ASHRAE 90.1 lighting power density (LPD) allowances — code-mandated maximum lighting power densities by space type and building type
| space type | building type | lpd W ft2 (W/ft2) | lpd W m2 (W/m2) | space description |
|---|---|---|---|---|
| gymnasium_exercise | common | 0.5 | 5.38 | Gymnasium - Exercise area |
| healthcare_exam_room | healthcare | 1.16 | 12.49 | Health Care - Exam/Treatment room |
| healthcare_nurse_station | healthcare | 0.75 | 8.07 | Health Care - Nurse's station |
| healthcare_patient_room | healthcare | 0.45 | 4.84 | Health Care - Patient room |
| healthcare_recovery_room | healthcare | 0.89 | 9.58 | Health Care - Recovery room |