Generator Sizing: 600 to 1500

Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.

Mechanical Engineeringrating_kw: 600 to 15005 rows
rating kwalt derate pct per 1000ft (%/1000ft)fuel consumption gph full load (gal/hr)notesphases (dimensionless)power factor (dimensionless)prime kw (kW)rated kva standby (kVA)rated voltage Vstandby kw (kW)starting skva (kVA)temp derate pct per 10C above 40C (%/10C)
6003.548600kW; 480V only at this size30.8540750277_4806004,2003
7503.560750kW; large industrial / mission critical30.8675938277_4807505,2503
1,0003.5791000kW; campus / mission critical; available in MV30.89001,250277_480_2400_41601,0007,0003
1,2503.5981250kW; MV output available30.81,1251,563277_480_2400_41601,2508,7503
1,5003.51181500kW; large campus / utility backup30.81,3501,875277_480_2400_41601,50010,5003