Generator Sizing: 100 to 200

Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.

Mechanical Engineeringrating_kw: 100 to 2005 rows
rating kwalt derate pct per 1000ft (%/1000ft)fuel consumption gph full load (gal/hr)notesphases (dimensionless)power factor (dimensionless)prime kw (kW)rated kva standby (kVA)rated voltage Vstandby kw (kW)starting skva (kVA)temp derate pct per 10C above 40C (%/10C)
1003.58.5100kW; most common commercial standby size30.890125120_208_240_4801007003
1253.510.5125kW30.8113156120_208_240_4801258753
1503.512.5150kW30.8135188120_208_240_4801501,0503
1753.514.5175kW30.8158219120_208_240_4801751,2253
2003.517200kW; large commercial30.8180250120_208_240_4802001,4003

This is a sample. Search the full generator sizing dataset and 300+ more by creating a free account and accessing the database.