Generator Sizing: 250 to 500

Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.

Mechanical Engineeringrating_kw: 250 to 5005 rows
rating kwalt derate pct per 1000ft (%/1000ft)fuel consumption gph full load (gal/hr)notesphases (dimensionless)power factor (dimensionless)prime kw (kW)rated kva standby (kVA)rated voltage Vstandby kw (kW)starting skva (kVA)temp derate pct per 10C above 40C (%/10C)
2503.521250kW30.8225313120_208_240_4802501,7503
3003.525300kW; industrial30.8270375120_208_240_4803002,1003
3503.529350kW30.8315438120_208_240_4803502,4503
4003.533400kW; medium industrial / data center30.8360500120_208_240_4804002,8003
5003.540500kW; large industrial30.8450625120_208_240_4805003,5003

This is a sample. Search the full generator sizing dataset and 300+ more by creating a free account and accessing the database.