Generator Sizing: 1500

Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.

Mechanical Engineeringrating kw: 15001 row
rating kwalt derate pct per 1000ft (%/1000ft)fuel consumption gph full load (gal/hr)phases (dimensionless)power factor (dimensionless)prime kw (kW)rated kva standby (kVA)rated voltage Vstandardstandby kw (kW)starting skva (kVA)temp derate pct per 10C above 40C (%/10C)
1,5003.511830.81,3501,875277 480 2400 4160NEMA MG1; Caterpillar C175 spec1,50010,5003