Generator Sizing: 60
Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.
| rating kw | alt derate pct per 1000ft (%/1000ft) | fuel consumption gph full load (gal/hr) | phases (dimensionless) | power factor (dimensionless) | prime kw (kW) | rated kva standby (kVA) | rated voltage V | standard | standby kw (kW) | starting skva (kVA) | temp derate pct per 10C above 40C (%/10C) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 60 | 3.5 | 5.5 | 3 | 0.8 | 54 | 75 | 120 208 240 480 | NEMA MG1; Cummins DSKAB spec | 60 | 450 | 3 |