Generator Sizing: 175

Standby and prime-rated diesel generator sizing data from 20kW to 2000kW per NEMA MG1 and ISO 8528-1. Includes standby vs prime kW, kVA rating, motor starting kVA (skVA), fuel consumption, altitude derating (3.5%/1000ft), and ambient temperature derating (3%/10C above 40C) per major manufacturer specifications.

Mechanical Engineeringrating kw: 1751 row
rating kwalt derate pct per 1000ft (%/1000ft)fuel consumption gph full load (gal/hr)phases (dimensionless)power factor (dimensionless)prime kw (kW)rated kva standby (kVA)rated voltage Vstandardstandby kw (kW)starting skva (kVA)temp derate pct per 10C above 40C (%/10C)
1753.514.530.8158219120 208 240 480NEMA MG1; Cummins DSKDA spec1751,2253