Generator Fuel Cell Specs: Synchronous Generator
temp rise class B armature resistance to tif limit 20000kva and above
Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications
| equipment type | spec parameter | condition | equipment category | manufacturer | parameter name | unit | value num | value str |
|---|---|---|---|---|---|---|---|---|
| Synchronous Generator | temp rise class B armature resistance | Class B - Armature all kVA resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 80 | 80 |
| Synchronous Generator | temp rise class B field resistance | Class B - Field winding resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 80 | 80 |
| Synchronous Generator | temp rise class F armature embedded 1563kva | Class F - Armature <= 1563 kVA embedded detector | generator | Caterpillar | Temperature Rise Limit | degC rise | 115 | 115 |
| Synchronous Generator | temp rise class F armature resistance | Class F - Armature all kVA resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 105 | 105 |
| Synchronous Generator | temp rise class F field resistance | Class F - Field winding resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 105 | 105 |
| Synchronous Generator | temp rise class H armature embedded 1563kva | Class H - Armature <= 1563 kVA embedded detector | generator | Caterpillar | Temperature Rise Limit | degC rise | 140 | 140 |
| Synchronous Generator | temp rise class H armature resistance | Class H - Armature all kVA resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 125 | 125 |
| Synchronous Generator | temp rise class H field resistance | Class H - Field winding resistance method | generator | Caterpillar | Temperature Rise Limit | degC rise | 125 | 125 |