Generator Fuel Cell Specs: Gaseous_Fuel_System_NG
Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications
| equipment type | spec parameter | equipment category | flow rate cfh (CFH) | fuel type | manufacturer | parameter name | pipe id in (in) | pipe size in (in) | run length ft (ft) | unit | value num | value str |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Gaseous_Fuel_System_NG | ng_pipe_size_0_75in_length_100ft | fuel_system | 79 | natural gas | Caterpillar | Natural Gas Iron Pipe Flow Capacity | 0.824 | 0.75 | 100 | CFH | 79 | 79 |
| Gaseous_Fuel_System_NG | ng_pipe_size_0_75in_length_10ft | fuel_system | 273 | natural gas | Caterpillar | Natural Gas Iron Pipe Flow Capacity | 0.824 | 0.75 | 10 | CFH | 273 | 273 |
| Gaseous_Fuel_System_NG | ng_pipe_size_0_75in_length_15ft | fuel_system | 219 | natural gas | Caterpillar | Natural Gas Iron Pipe Flow Capacity | 0.824 | 0.75 | 15 | CFH | 219 | 219 |