Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications
| equipment type | spec parameter | condition | equipment category | manufacturer | parameter name | temperature c (degC) | temperature f (degF) | unit | value str |
|---|---|---|---|---|---|---|---|---|---|
| Synchronous_Generator | insulation_class_A_max_temp | Class A | generator | Caterpillar | Insulation Class Maximum Operating Temperature | 105 | 221 | degC | 105 |
| Synchronous_Generator | insulation_class_B_max_temp | Class B | generator | Caterpillar | Insulation Class Maximum Operating Temperature | 130 | 266 | degC | 130 |
| Synchronous_Generator | insulation_class_F_max_temp | Class F | generator | Caterpillar | Insulation Class Maximum Operating Temperature | 155 | 311 | degC | 155 |