Generator Fuel Cell Specs: Synchronous Generator
reactance subtransient xdpp max to synchronous speed 12pole 60hz
Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications
| equipment type | spec parameter | condition | equipment category | manufacturer | parameter name | unit | value num | value str |
|---|---|---|---|---|---|---|---|---|
| Synchronous Generator | reactance subtransient xdpp max | maximum | generator | Caterpillar | Sub-transient Reactance Xdpp | pu | 0.26 | 0.26 |
| Synchronous Generator | reactance subtransient xdpp min | minimum | generator | Caterpillar | Sub-transient Reactance Xdpp | pu | 0.08 | 0.08 |
| Synchronous Generator | reactance synchronous xd max | maximum | generator | Caterpillar | Synchronous Reactance Xd | pu | 3.9 | 3.9 |
| Synchronous Generator | reactance synchronous xd min | minimum | generator | Caterpillar | Synchronous Reactance Xd | pu | 2 | 2.0 |
| Synchronous Generator | reactance transient xdp max | maximum | generator | Caterpillar | Transient Reactance Xdp | pu | 0.45 | 0.45 |
| Synchronous Generator | reactance transient xdp min | minimum | generator | Caterpillar | Transient Reactance Xdp | pu | 0.16 | 0.16 |
| Synchronous Generator | reactance zero sequence x0 max | maximum | generator | Caterpillar | Zero Sequence Reactance X0 | pu | 0.25 | 0.25 |
| Synchronous Generator | reactance zero sequence x0 min | minimum | generator | Caterpillar | Zero Sequence Reactance X0 | pu | 0.02 | 0.02 |