Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Generator Fuel Cell Specs: Gaseous Fuel System LPGV

lpgv fitting equiv 4in tee branch to lpgv pipe size 0 75in length 40ft

Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications

Electrical Engineeringequipment type: Gaseous Fuel System LPGV10 rowsPage 4 of 10
equipment typespec parameterequipment categoryflow rate cfh (CFH)fuel typemanufacturerparameter namepipe id in (in)pipe size in (in)run length ft (ft)unitvalue numvalue str
Gaseous Fuel System LPGVlpgv fitting equiv 4in tee branchfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through branch4.0264ft equivalent length20.120.1
Gaseous Fuel System LPGVlpgv fitting equiv 4in tee runfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through run4.0264ft equivalent length6.76.7
Gaseous Fuel System LPGVlpgv fitting equiv 6in elbow45fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 45 degree elbow6.0656ft equivalent length8.18.1
Gaseous Fuel System LPGVlpgv fitting equiv 6in elbow90fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 degree elbow6.0656ft equivalent length15.215.2
Gaseous Fuel System LPGVlpgv fitting equiv 6in tee branchfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through branch6.0656ft equivalent length30.330.3
Gaseous Fuel System LPGVlpgv fitting equiv 6in tee runfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through run6.0656ft equivalent length10.110.1
Gaseous Fuel System LPGVlpgv pipe size 0 75in length 10ftfuel system241LPG-VCaterpillarLPG-Vapor Iron Pipe Flow Capacity0.8240.7510CFH241241
Gaseous Fuel System LPGVlpgv pipe size 0 75in length 20ftfuel system166LPG-VCaterpillarLPG-Vapor Iron Pipe Flow Capacity0.8240.7520CFH166166
Gaseous Fuel System LPGVlpgv pipe size 0 75in length 30ftfuel system133LPG-VCaterpillarLPG-Vapor Iron Pipe Flow Capacity0.8240.7530CFH133133
Gaseous Fuel System LPGVlpgv pipe size 0 75in length 40ftfuel system114LPG-VCaterpillarLPG-Vapor Iron Pipe Flow Capacity0.8240.7540CFH114114

What else is in Engineering Database