Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Generator Fuel Cell Specs: Gaseous Fuel System LPGV

lpgv fitting equiv 1 5in tee branch to lpgv fitting equiv 2 5in tee run

Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications

Electrical Engineeringequipment type: Gaseous Fuel System LPGV10 rowsPage 2 of 10
equipment typespec parameterequipment categoryfuel typemanufacturerparameter namepipe id in (in)pipe size in (in)unitvalue numvalue str
Gaseous Fuel System LPGVlpgv fitting equiv 1 5in tee branchfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through branch1.611.5ft equivalent length88.0
Gaseous Fuel System LPGVlpgv fitting equiv 1 5in tee runfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through run1.611.5ft equivalent length2.72.7
Gaseous Fuel System LPGVlpgv fitting equiv 1in elbow45fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 45 degree elbow1.0491ft equivalent length1.231.23
Gaseous Fuel System LPGVlpgv fitting equiv 1in elbow90fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 degree elbow1.0491ft equivalent length2.62.6
Gaseous Fuel System LPGVlpgv fitting equiv 1in tee branchfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through branch1.0491ft equivalent length5.35.3
Gaseous Fuel System LPGVlpgv fitting equiv 1in tee runfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through run1.0491ft equivalent length1.81.8
Gaseous Fuel System LPGVlpgv fitting equiv 2 5in elbow45fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 45 degree elbow2.4692.5ft equivalent length2.92.9
Gaseous Fuel System LPGVlpgv fitting equiv 2 5in elbow90fuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 degree elbow2.4692.5ft equivalent length6.26.2
Gaseous Fuel System LPGVlpgv fitting equiv 2 5in tee branchfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through branch2.4692.5ft equivalent length12.412.4
Gaseous Fuel System LPGVlpgv fitting equiv 2 5in tee runfuel systemLPG-VCaterpillarLPG-V Iron Pipe Fitting Equivalent Length - 90 deg tee flow through run2.4692.5ft equivalent length4.14.1