Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Generator Fuel Cell Specs: Bloom Energy ES5

es5 grid interconnect to es5 seismic rating

Generator system design data and fuel cell specifications for datacenter backup power — Caterpillar synchronous generator specs (synchronous speeds, insulation classes, IP ratings, temperature rise, TIF weighting, reactances, pitch factors, overspeed limits), Caterpillar gaseous fuel system pipe sizing (NG and LPG-V iron pipe flow capacities, fitting equivalent lengths, specific gravity multipliers, LPG tank vaporization capacities), Bloom Energy ES5 200kW and Server 325kW solid oxide fuel cell specifications

Electrical Engineeringequipment type: Bloom Energy ES510 rowsPage 2 of 3
equipment typespec parameterconditionequipment categoryfrequency hz (Hz)manufacturerparameter namepower kw (kW)unitvalue numvalue strvoltage v (V)
Bloom Energy ES5es5 grid interconnectfuel cellBloom EnergyGrid Interconnect StandardsRule 21; IEEE 1547
Bloom Energy ES5es5 heat rate hhv maxmaximum (lowest efficiency)fuel cellBloom EnergyHeat Rate HHVBtu/kWh7,1277127
Bloom Energy ES5es5 heat rate hhv minminimum (highest efficiency)fuel cellBloom EnergyHeat Rate HHVBtu/kWh5,8115811
Bloom Energy ES5es5 humidity rangefuel cellBloom EnergyRelative Humidity Range0-100%
Bloom Energy ES5es5 locationfuel cellBloom EnergyInstallation LocationOutdoor
Bloom Energy ES5es5 nameplate outputfuel cell60Bloom EnergyNameplate Power Output Net AC200kW200200 kW480
Bloom Energy ES5es5 noise levelat 6 ft (1.83 m)fuel cellBloom EnergyNoise LeveldBA< 70 dBA at 6 feet
Bloom Energy ES5es5 nox emissionsfuel cellBloom EnergyNOx Emissionslbs/MWh< 0.01 lbs/MWh
Bloom Energy ES5es5 safety listingfuel cellBloom EnergySafety CertificationUL Category IRGZ; UL File MH45102; ANSI/CSA FC1-2014
Bloom Energy ES5es5 seismic ratingfuel cellBloom EnergySeismic RatingIBC site class D

What else is in Engineering Database