Fire Sprinkler Protection: sprinkler head
K5.6 135F QR pendent to K8.0 175F pendent
Fire sprinkler K-factors, coverage areas, fire resistance assembly ratings, and clean/suppression agent properties — per NFPA 13, NFPA 2001, NFPA 12, UL Fire Resistance Directory, ACI 216.1
| record type | record id | coverage area ft2 (ft2) | deflector type | flow at min pressure gpm (gal/min) | k factor (gpm/psi^0.5) | max spacing ft (ft) | min pressure psi (psi) | orifice size in (in) | orifice size mm (mm) | response type | standard | subcategory | temperature rating C | temperature rating F (degF) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| sprinkler head | K5.6 135F QR pendent | 200 | pendent | 14.8 | 5.6 | 15 | 7 | 0.5 | 12.7 | quick response | NFPA 13 2022 Sec. 19.2.3.1; UL 199 | sprinkler head | 57 | 135 |
| sprinkler head | K5.6 135F pendent | 130 | pendent | 14.8 | 5.6 | 15 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Sec. 19.2; UL 199; NFPA 13 Table 6.2.3.1 | sprinkler head | 57 | 135 |
| sprinkler head | K5.6 135F sidewall | 120 | sidewall | 14.8 | 5.6 | 14 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Sec. 8.4.5; UL 1626 | sprinkler head | 57 | 135 |
| sprinkler head | K5.6 135F upright | 130 | upright | 14.8 | 5.6 | 15 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Sec. 8.4; UL 199 | sprinkler head | 57 | 135 |
| sprinkler head | K5.6 155F pendent | 130 | pendent | 14.8 | 5.6 | 15 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Sec. 19.2; UL 199 | sprinkler head | 68 | 155 |
| sprinkler head | K5.6 286F pendent | 100 | pendent | 14.8 | 5.6 | 15 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Table 6.2.3.1; NFPA 96 | sprinkler head | 141 | 286 |
| sprinkler head | K5.6 360F pendent | 100 | pendent | 14.8 | 5.6 | 12 | 7 | 0.5 | 12.7 | standard | NFPA 13 2022 Table 6.2.3.1 | sprinkler head | 182 | 360 |
| sprinkler head | K8.0 155F pendent | 130 | pendent | 21.2 | 8 | 15 | 7 | 0.531 | 13.5 | standard | NFPA 13 2022 Sec. 12.2.3; NFPA 13 Table 6.2.3.1 | sprinkler head | 68 | 155 |
| sprinkler head | K8.0 175F pendent | 130 | pendent | 21.2 | 8 | 15 | 7 | 0.531 | 13.5 | standard | NFPA 13 2022 Sec. 12.2.3; UL 199 | sprinkler head | 79 | 175 |
What else is in Engineering Database
Iron Engine ↗Engineering AI at ironengine.ai
AI built for engineering. Searches the engineering database, performs calculations, gives source-backed engineering insights.
Get started for free ↗Reference Data375 engineering tablesMaterial properties, pipe and shape dimensions, code tables, and electrical ratings across mechanical, civil, chemical, electrical, materials, and manufacturing engineering.
Browse dataCalculatorsDeterministic engineering calculatorsSizing, checking, and conversion tools that run against the reference tables. Inputs are code-compliant, outputs are traceable to the source standard.
Browse calculators