Fire Sprinkler Protection: sprinkler head

K5.6 135F QR pendent to K8.0 175F pendent

Fire sprinkler K-factors, coverage areas, fire resistance assembly ratings, and clean/suppression agent properties — per NFPA 13, NFPA 2001, NFPA 12, UL Fire Resistance Directory, ACI 216.1

Mechanical Engineeringrecord type: sprinkler head9 rowsPage 2 of 2
record typerecord idcoverage area ft2 (ft2)deflector typeflow at min pressure gpm (gal/min)k factor (gpm/psi^0.5)max spacing ft (ft)min pressure psi (psi)orifice size in (in)orifice size mm (mm)response typestandardsubcategorytemperature rating Ctemperature rating F (degF)
sprinkler headK5.6 135F QR pendent200pendent14.85.61570.512.7quick responseNFPA 13 2022 Sec. 19.2.3.1; UL 199sprinkler head57135
sprinkler headK5.6 135F pendent130pendent14.85.61570.512.7standardNFPA 13 2022 Sec. 19.2; UL 199; NFPA 13 Table 6.2.3.1sprinkler head57135
sprinkler headK5.6 135F sidewall120sidewall14.85.61470.512.7standardNFPA 13 2022 Sec. 8.4.5; UL 1626sprinkler head57135
sprinkler headK5.6 135F upright130upright14.85.61570.512.7standardNFPA 13 2022 Sec. 8.4; UL 199sprinkler head57135
sprinkler headK5.6 155F pendent130pendent14.85.61570.512.7standardNFPA 13 2022 Sec. 19.2; UL 199sprinkler head68155
sprinkler headK5.6 286F pendent100pendent14.85.61570.512.7standardNFPA 13 2022 Table 6.2.3.1; NFPA 96sprinkler head141286
sprinkler headK5.6 360F pendent100pendent14.85.61270.512.7standardNFPA 13 2022 Table 6.2.3.1sprinkler head182360
sprinkler headK8.0 155F pendent130pendent21.281570.53113.5standardNFPA 13 2022 Sec. 12.2.3; NFPA 13 Table 6.2.3.1sprinkler head68155
sprinkler headK8.0 175F pendent130pendent21.281570.53113.5standardNFPA 13 2022 Sec. 12.2.3; UL 199sprinkler head79175