Fire Sprinkler Protection: sprinkler_head

Fire sprinkler K-factors, coverage areas, fire resistance assembly ratings, and clean/suppression agent properties — per NFPA 13, NFPA 2001, NFPA 12, UL Fire Resistance Directory, ACI 216.1

Mechanical Engineeringrecord_type: sprinkler_head3 rows
record typerecord idcoverage area ft2 (ft2)deflector typeflow at min pressure gpm (gal/min)k factor (gpm/psi^0.5)max spacing ft (ft)min pressure psi (psi)notesorifice size in (in)orifice size mm (mm)response typesubcategorytemperature rating Ctemperature rating F (degF)
sprinkler_headK11.2_155F_QR_pendent130pendent29.611.2157K11.2 QR pendent; improved suppression performance; for light/ordinary hazard at higher design densities0.62515.9quick_responsesprinkler_head68155
sprinkler_headK11.2_155F_pendent100pendent29.611.2157K11.2; extra hazard/storage; Q=11.2*sqrt(7)=29.6 gpm; required for storage density ≥0.34 gpm/ft2; NFPA 13 12.2.30.62515.9standardsprinkler_head68155
sprinkler_headK11.2_175F_pendent100pendent29.611.2157K11.2 High temp; storage/extra hazard applications0.62515.9standardsprinkler_head79175