Fire Sprinkler Protection: fire_resistance

Fire sprinkler K-factors, coverage areas, fire resistance assembly ratings, and clean/suppression agent properties — per NFPA 13, NFPA 2001, NFPA 12, UL Fire Resistance Directory, ACI 216.1

Mechanical Engineeringrecord_type: fire_resistance3 rows
record typerecord idUL design number exampleassembly descriptionassembly typemin thickness in (in)notesrating hours (hr)subcategory
fire_resistanceconcrete_slab_1hrACI 216.1 Table 4.4.2One-hour fire-rated concrete slab: Normal-weight concrete (NWC) slab 3.5 in thick minimum; or lightweight concrete (LWC) 3.2 in thick minimum. Tested per ASTM E119. Restrained and unrestrained assembly.concrete_slab_1hr3.5Cover to bottom reinforcement min 0.75 in; NWC density 145 pcf; calcareous aggregate1fire_resistance
fire_resistanceconcrete_slab_2hrACI 216.1 Table 4.4.2Two-hour fire-rated concrete slab: NWC slab 4.5 in thick minimum; or LWC 4.0 in thick minimum. Tested per ASTM E119 unrestrained.concrete_slab_2hr4.5Reinforcing cover increased for 2-hr; typical residential floor slab or parking deck2fire_resistance
fire_resistancegypsum_wall_1hrUL Design U305One-hour fire-rated partition: 2x4 wood studs @ 16 in OC, one layer 5/8 in Type X gypsum board each side. Min stud size 2x4 nominal, no cavity insulation required. Tested per ASTM E119 / UL 263.gypsum_wall_1hr1.25Based on ASTM E119 testing; 5/8 in Type X gypsum is critical; framing protected by gypsum layer1fire_resistance