Explore the Engineering Database more efficiently by signing up for free. Sign up free

H21-310 — Heat Exchanger

Equipment Type
Heat Exchanger
Class Code
H21-310
Description
Heat exchanger, radiator, Small
Failure Rate per Year (failures/year)
0.036077
Failures (count)
65
Mdt Hours (h)
0.6
Mtbf Hours (h)
242,817
Mttm Hours (h)
0.23
Mttr Hours (h)
12.55
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
1,801.7

Source: IEEE Std 3006.8-2018 Table 2

Heat_Exchanger — class code H21-310 · description Heat exchanger, radiator, small · failure rate per year 0.0360766 failures/year · mtbf hours 242817 h · unit years 1801.7 unit-years | Equipment Failure Rates | Engineering Database