H21-100 — Heat Exchanger
- Equipment Type
- Heat Exchanger
- Class Code
- H21-100
- Description
- Heat exchanger, Boiler system,
- Failure Rate per Year (failures/year)
- 0.170129
- Failures (count)
- 164
- Mdt Hours (h)
- 19.15
- Mtbf Hours (h)
- 51,490
- Mttm Hours (h)
- 18.15
- Mttr Hours (h)
- 7.22
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 964
Source: IEEE Std 3006.8-2018 Table 2