E22-000 — Generator
- Equipment Type
- Generator
- Class Code
- E22-000
- Description
- Generator, Steam Turbine
- Failure Rate per Year (failures/year)
- 1.107687
- Failures (count)
- 130
- Mdt Hours (h)
- 263.61
- Mtbf Hours (h)
- 7,908
- Mttm Hours (h)
- 288.24
- Mttr Hours (h)
- 100.59
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 117.4
Source: IEEE Std 3006.8-2018 Table 2