Explore the Engineering Database more efficiently by signing up for free. Sign up free

E19-112 — Generator

Equipment Type
Generator
Class Code
E19-112
Description
Generator, Gas turbine,
Failure Rate per Year (failures/year)
0.184526
Failures (count)
113
Mdt Hours (h)
4.42
Mtbf Hours (h)
47,473
Mttm Hours (h)
4.4
Mttr Hours (h)
6.05
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
612.4

Source: IEEE Std 3006.8-2018 Table 2

Generator — class code E19-112 · mtbf hours 47473 h · failure rate per year 0.184526 failures/year · unit years 612.4 unit-years · failures 113 count | Equipment Failure Rates | Engineering Database