E19-211 — Generator
- Equipment Type
- Generator
- Class Code
- E19-211
- Description
- Generator, Gas turbine,
- Failure Rate per Year (failures/year)
- 0.414186
- Failures (count)
- 77
- Mdt Hours (h)
- 15.87
- Mtbf Hours (h)
- 21,150
- Mttm Hours (h)
- 13.26
- Mttr Hours (h)
- 50.33
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 185.9
Source: IEEE Std 3006.8-2018 Table 2