Explore the Engineering Database more efficiently by signing up for free. Sign up free
H10-321 — Chiller
- Equipment Type
- Chiller
- Class Code
- H10-321
- Description
- Chiller, reciprocating, closed,
- Failure Rate per Year (failures/year)
- 0.157633
- Failures (count)
- 139
- Mdt Hours (h)
- 2.06
- Mtbf Hours (h)
- 55,572
- Mttm Hours (h)
- 1.53
- Mttr Hours (h)
- 11.11
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 881.8
Source: IEEE Std 3006.8-2018 Table 2