H10-100 — Chiller

Equipment Type
Chiller
Class Code
H10-100
Description
Chiller, Absorption
Failure Rate per Year (failures/year)
0.158231
Failures (count)
93
Mdt Hours (h)
0.72
Mtbf Hours (h)
55,362
Mttm Hours (h)
0.68
Mttr Hours (h)
11.4
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
587.7

Source: IEEE Std 3006.8-2018 Table 2