Effectiveness Ntu: Crossflow Cmin mixed
0.75 1.0 to 1.00 1.0
Heat exchanger effectiveness (ε) vs. number of transfer units (NTU) and capacity ratio (Cr = Cmin/Cmax) for seven flow configurations: parallel-flow, counterflow, shell-and-tube 1-pass, shell-and-tube 2-pass, crossflow both unmixed, crossflow Cmin mixed, crossflow Cmax mixed. Data digitized from Incropera Figures 11.10-11.15.
| hx configuration | sk | capacity ratio (dimensionless) | effectiveness (dimensionless) | mixed fluid | ntu (dimensionless) |
|---|---|---|---|---|---|
| Crossflow Cmin mixed | 0.75 1.0 | 0.75 | 0.52 | C min | 1 |
| Crossflow Cmin mixed | 0.75 1.5 | 0.75 | 0.65 | C min | 1.5 |
| Crossflow Cmin mixed | 0.75 2.0 | 0.75 | 0.73 | C min | 2 |
| Crossflow Cmin mixed | 0.75 2.5 | 0.75 | 0.78 | C min | 2.5 |
| Crossflow Cmin mixed | 0.75 3.0 | 0.75 | 0.82 | C min | 3 |
| Crossflow Cmin mixed | 0.75 4.0 | 0.75 | 0.88 | C min | 4 |
| Crossflow Cmin mixed | 0.75 5.0 | 0.75 | 0.91 | C min | 5 |
| Crossflow Cmin mixed | 1.00 0.0 | 1 | 0 | C min | 0 |
| Crossflow Cmin mixed | 1.00 0.5 | 1 | 0.33 | C min | 0.5 |
| Crossflow Cmin mixed | 1.00 1.0 | 1 | 0.5 | C min | 1 |