Effectiveness Ntu: Crossflow Cmin mixed

0.75 1.0 to 1.00 1.0

Heat exchanger effectiveness (ε) vs. number of transfer units (NTU) and capacity ratio (Cr = Cmin/Cmax) for seven flow configurations: parallel-flow, counterflow, shell-and-tube 1-pass, shell-and-tube 2-pass, crossflow both unmixed, crossflow Cmin mixed, crossflow Cmax mixed. Data digitized from Incropera Figures 11.10-11.15.

Mechanical Engineeringhx configuration: Crossflow Cmin mixed10 rowsPage 3 of 4
hx configurationskcapacity ratio (dimensionless)effectiveness (dimensionless)mixed fluidntu (dimensionless)
Crossflow Cmin mixed0.75 1.00.750.52C min1
Crossflow Cmin mixed0.75 1.50.750.65C min1.5
Crossflow Cmin mixed0.75 2.00.750.73C min2
Crossflow Cmin mixed0.75 2.50.750.78C min2.5
Crossflow Cmin mixed0.75 3.00.750.82C min3
Crossflow Cmin mixed0.75 4.00.750.88C min4
Crossflow Cmin mixed0.75 5.00.750.91C min5
Crossflow Cmin mixed1.00 0.010C min0
Crossflow Cmin mixed1.00 0.510.33C min0.5
Crossflow Cmin mixed1.00 1.010.5C min1