Duct Construction Specs: leakage class

CL6 Q2 to CL6 Q5

ASHRAE duct construction specifications: sheet metal gauge thickness and weight for galvanized, uncoated, and stainless steel ductwork; duct leakage percentages by leakage class and flow ratio; and maximum allowable fan system leakage by HVAC system type

Mechanical Engineeringdata type: leakage class5 rowsPage 3 of 3
data typegageleakage class (dimensionless)leakage pct at 0p5 inwg (%)leakage pct at 10 inwg (%)leakage pct at 1 inwg (%)leakage pct at 2 inwg (%)leakage pct at 3 inwg (%)leakage pct at 4 inwg (%)leakage pct at 5 inwg (%)leakage pct at 6 inwg (%)leakage pct at 8 inwg (%)qfan per as cfm per ft2 (cfm/ft2)
leakage classCL6 Q261.913.434.76.17.48.59.611.62
leakage classCL6 Q2p561.510.72.43.84.95.96.87.79.32.5
leakage classCL6 Q361.38.923.14.14.95.76.47.73
leakage classCL6 Q4616.71.52.43.13.74.34.85.84
leakage classCL6 Q560.85.41.21.92.533.43.84.65