Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Duct Construction Specs: leakage class

CL3 Q2 to CL4 Q5

ASHRAE duct construction specifications: sheet metal gauge thickness and weight for galvanized, uncoated, and stainless steel ductwork; duct leakage percentages by leakage class and flow ratio; and maximum allowable fan system leakage by HVAC system type

Mechanical Engineeringdata type: leakage class10 rowsPage 2 of 3
data typegageleakage class (dimensionless)leakage pct at 0p5 inwg (%)leakage pct at 10 inwg (%)leakage pct at 1 inwg (%)leakage pct at 2 inwg (%)leakage pct at 3 inwg (%)leakage pct at 4 inwg (%)leakage pct at 5 inwg (%)leakage pct at 6 inwg (%)leakage pct at 8 inwg (%)qfan per as cfm per ft2 (cfm/ft2)
leakage classCL3 Q2316.71.52.43.13.74.34.85.82
leakage classCL3 Q2p530.85.41.21.92.533.43.84.62.5
leakage classCL3 Q330.64.511.622.52.83.23.93
leakage classCL3 Q430.53.40.81.21.51.82.12.42.94
leakage classCL3 Q530.42.70.60.91.21.51.71.92.35
leakage classCL4 Q241.38.923.14.14.95.76.47.72
leakage classCL4 Q2p5417.11.62.53.33.94.65.16.22.5
leakage classCL4 Q340.861.32.12.73.33.84.35.23
leakage classCL4 Q440.64.511.622.52.83.23.94
leakage classCL4 Q540.53.60.81.31.622.32.63.15