Duct Construction Specs: uncoated_steel_gauge

ASHRAE duct construction specifications: sheet metal gauge thickness and weight for galvanized, uncoated, and stainless steel ductwork; duct leakage percentages by leakage class and flow ratio; and maximum allowable fan system leakage by HVAC system type

Mechanical Engineeringdata_type: uncoated_steel_gauge3 rows
data typegagemin thickness cold rolled in (in)min thickness hot rolled in (in)nominal thickness in (in)nominal weight lb per ft2 (lb/ft2)
uncoated_steel_gauge100.12850.12650.13455.625
uncoated_steel_gauge110.11360.11160.11965
uncoated_steel_gauge120.09860.09660.10464.375

This is a sample. Search the full duct construction specs dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE