Cooling Tower Performance: induced_draft_crossflow

Cooling tower performance data — typical approach temperature, range, nominal tons per cell, GPM per ton, and air flow CFM per ton by tower type and capacity range

Mechanical Engineeringtower_type: induced_draft_crossflow3 rows
tower typedesign wet bulb or capacityair flow cfm per ton (cfm/ton)approach F (F)gpm per ton (gpm/ton)nominal tons per cell (tons)notesrange F (F)
induced_draft_crossflowhighrise_hotclimate_120F_approach38053200Hot-climate high-rise; design WBT=85F; approach must increase in warmer climates10
induced_draft_crossflowlarge_500_2000_tons310731,000Large induced draft crossflow; multi-cell configuration; lower fan horsepower per ton10
induced_draft_crossflowmedium_150_500_tons33073300Medium induced draft crossflow; design conditions 95/85/78 (entering/leaving/WBT)10

This is a sample. Search the full cooling tower performance dataset and 300+ more by creating a free account and accessing the database.