Cooling tower performance data — typical approach temperature, range, nominal tons per cell, GPM per ton, and air flow CFM per ton by tower type and capacity range
| tower type | design wet bulb or capacity | air flow cfm per ton (cfm/ton) | approach F (F) | gpm per ton (gpm/ton) | nominal tons per cell (tons) | notes | range F (F) |
|---|---|---|---|---|---|---|---|
| induced_draft_crossflow | highrise_hotclimate_120F_approach | 380 | 5 | 3 | 200 | Hot-climate high-rise; design WBT=85F; approach must increase in warmer climates | 10 |
| induced_draft_crossflow | large_500_2000_tons | 310 | 7 | 3 | 1,000 | Large induced draft crossflow; multi-cell configuration; lower fan horsepower per ton | 10 |
| induced_draft_crossflow | medium_150_500_tons | 330 | 7 | 3 | 300 | Medium induced draft crossflow; design conditions 95/85/78 (entering/leaving/WBT) | 10 |