Cooling Tower Performance: forced_draft_counterflow

Cooling tower performance data — typical approach temperature, range, nominal tons per cell, GPM per ton, and air flow CFM per ton by tower type and capacity range

Mechanical Engineeringtower_type: forced_draft_counterflow2 rows
tower typedesign wet bulb or capacityair flow cfm per ton (cfm/ton)approach F (F)gpm per ton (gpm/ton)nominal tons per cell (tons)notesrange F (F)
forced_draft_counterflowmedium_100_400_tons38083200Medium forced draft counterflow; fan noise on inlet is lower-frequency issue10
forced_draft_counterflowsmall_25_100_tons4008360Forced draft (blow-through) counterflow; fan on inlet; higher inlet air velocity; noisier than induced draft; smaller plan area10