Cooling Tower Performance: induced_draft_counterflow

Cooling tower performance data — typical approach temperature, range, nominal tons per cell, GPM per ton, and air flow CFM per ton by tower type and capacity range

Mechanical Engineeringtower_type: induced_draft_counterflow3 rows
tower typedesign wet bulb or capacityair flow cfm per ton (cfm/ton)approach F (F)gpm per ton (gpm/ton)nominal tons per cell (tons)notesrange F (F)
induced_draft_counterflowlarge_800_plus_tons330531,500Large counterflow; approach can be tightened with more fill depth and airflow10
induced_draft_counterflowmedium_200_800_tons35063400Medium induced draft counterflow; preferred for close-approach requirements10
induced_draft_counterflowsmall_50_200_tons37063125Induced draft counterflow; counter-airflow slightly better thermal effectiveness; smaller footprint than crossflow; typical 95/85/78 design10

This is a sample. Search the full cooling tower performance dataset and 300+ more by creating a free account and accessing the database.