Circuit Breaker Ratings: mccb_endurance_ops

Circuit breaker ratings and application data per IEEE C37.06-2009 (medium/high-voltage power CBs) and IEEE Std 3004.5-2025 (low-voltage LVPCB and MCCB). Covers MV/HV preferred ratings (interrupting, TRV, close-latch), LV frame and trip-device ratings, LVPCB short-circuit ratings with and without instantaneous trip, X/R multiplying factors for fault-current derating, altitude derating factors, and MCCB electrical endurance operation counts.

Electrical Engineeringvoltage_class: mccb_endurance_ops3 rows
voltage classinterrupting kAbreaker typeframe size A (A)ops per min (ops/min)ops with current (operations)ops without current (operations)standardtotal ops (operations)
mccb_endurance_ops100MCCB10066,0004,000IEEE Std 3004.5-202510,000
mccb_endurance_ops150MCCB15054,0004,000IEEE Std 3004.5-20258,000
mccb_endurance_ops225MCCB22554,0004,000IEEE Std 3004.5-20258,000