Busway Specs: Schneider I-Line II
630A copper IEC/EN 61439-6 to 800A copper IEC/EN 61439-6
Busway (bus duct / busbar trunking) electrical ratings, impedance, dimensional, and weight data for four manufacturers: Eaton Pow-R-Way III (UL 857 and IEC 439), Schneider I-Line II and I-Line II Contact (IEC/EN 61439-6), Schneider Canalis KR (IEC), Starline Series HP (UL 857 and IEC), and Starline TrackBusway 1000T5M (UL 857). Covers 225–6300A copper and aluminum, 600V–1500V.
| manufacturer series | rating config | ampere rating a (A) | conductor material | housing width mm (mm) | impedance mohm per m (mΩ/m) | ip rating | phases | reactance mohm per m (mΩ/m) | resistance mohm per m (mΩ/m) | short circuit duration | short circuit rating ka (kA) | standard | vd pf100 v per m (V/m) | voltage rating v | weight 3w kg per m (kg/m) | weight 4w 100n kg per m (kg/m) | weight 4w 200n kg per m (kg/m) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Schneider I-Line II | 630A copper IEC/EN 61439-6 | 630 | copper | 98 | 0.079 | IP54 | 3 | 0.032 | 0.073 | 1-second rms sym | 40 | IEC/EN 61439-6 | 0.08 | 1000 | 14.5 | 16.9 | 18.5 |
| Schneider I-Line II | 800A copper IEC/EN 61439-6 | 800 | copper | 98 | 0.084 | IP54 | 3 | 0.033 | 0.077 | 1-second rms sym | 40 | IEC/EN 61439-6 | 0.107 | 1000 | 14.5 | 16.9 | 18.5 |
What else is in Engineering Database
AI built for engineering. Searches the engineering database, performs calculations, gives source-backed engineering insights.
Get started for free ↗Reference Data375 engineering tablesMaterial properties, pipe and shape dimensions, code tables, and electrical ratings across mechanical, civil, chemical, electrical, materials, and manufacturing engineering.
Browse dataCalculatorsDeterministic engineering calculatorsSizing, checking, and conversion tools that run against the reference tables. Inputs are code-compliant, outputs are traceable to the source standard.
Browse calculators