Home/Reference Data/Busway Specs/Schneider_I-Line_II

Busway Specs: Schneider_I-Line_II

Busway (bus duct / busbar trunking) electrical ratings, impedance, dimensional, and weight data for four manufacturers: Eaton Pow-R-Way III (UL 857 and IEC 439), Schneider I-Line II and I-Line II Contact (IEC/EN 61439-6), Schneider Canalis KR (IEC), Starline Series HP (UL 857 and IEC), and Starline TrackBusway 1000T5M (UL 857). Covers 225–6300A copper and aluminum, 600V–1500V.

Electrical Engineeringmanufacturer_series: Schneider_I-Line_II3 rows
manufacturer seriesrating configampere rating a (A)conductor materialhousing width mm (mm)impedance mohm per m (mΩ/m)ip ratingphasesreactance mohm per m (mΩ/m)resistance mohm per m (mΩ/m)short circuit durationshort circuit rating ka (kA)standardvd pf100 v per m (V/m)voltage rating vweight 3w kg per m (kg/m)weight 4w 100n kg per m (kg/m)weight 4w 200n kg per m (kg/m)
Schneider_I-Line_II1000A_copper_IEC/EN 61439-61,000copper980.082IP5430.0310.0761-second rms sym50IEC/EN 61439-60.13100015.517.819.4
Schneider_I-Line_II1250A_copper_IEC/EN 61439-61,250copper1100.058IP5430.0270.0521-second rms sym65IEC/EN 61439-60.113100020.524.926.9
Schneider_I-Line_II1350A_copper_IEC/EN 61439-61,350copper1200.044IP5430.020.0391-second rms sym65IEC/EN 61439-60.089100021.527.629.8