Home/Reference Data/Busway Specs/Eaton_Pow-R-Way_III

Busway Specs: Eaton_Pow-R-Way_III

Busway (bus duct / busbar trunking) electrical ratings, impedance, dimensional, and weight data for four manufacturers: Eaton Pow-R-Way III (UL 857 and IEC 439), Schneider I-Line II and I-Line II Contact (IEC/EN 61439-6), Schneider Canalis KR (IEC), Starline Series HP (UL 857 and IEC), and Starline TrackBusway 1000T5M (UL 857). Covers 225–6300A copper and aluminum, 600V–1500V.

Electrical Engineeringmanufacturer_series: Eaton_Pow-R-Way_III3 rows
manufacturer seriesrating configampere rating a (A)bar depth mm (mm)bar width mm (mm)bars per phaseconductor materialcurrent density a per cm2 (A/cm²)housing height mm (mm)housing width mm (mm)impedance mohm per m (mΩ/m)ip ratingphasesreactance mohm per m (mΩ/m)resistance mohm per m (mΩ/m)short circuit durationshort circuit rating ka (kA)standardvoltage rating vweight 3w kg per m (kg/m)weight 4w 100n kg per m (kg/m)weight 4w 200n kg per m (kg/m)
Eaton_Pow-R-Way_III1000A_aluminum_IEC 4391,0006.441.11aluminum111.3120.792.1IP40319.7901-second rms sym45IEC 43910007911
Eaton_Pow-R-Way_III1000A_aluminum_UL 8571,0006.457.21aluminum2.4430.842.296-cycle rms sym100UL 8576007911
Eaton_Pow-R-Way_III1000A_copper_IEC 4391,0006.441.11copper380111.3120.785.2IP4032780.81-second rms sym35IEC 4391000121517

This is a sample. Search the full busway specs dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE

Related data