| equipment class | voltage class | electrode config | enclosure depth mm (mm) | enclosure height mm (mm) | enclosure width mm (mm) | gap mm (mm) | insulation level pct (%) | notes | working distance in (in) | working distance mm (mm) |
|---|---|---|---|---|---|---|---|---|---|---|
| panelboard | 15KV | VCB | 508 | 914 | 762 | 152 | 100 | 15kV distribution panelboard / metering panel; IEEE 1584-2018 lacks a dedicated MV panelboard class — MV switchgear parameters applied per standard guidance; enclosure dimensions AI-estimated from typical MV panel | 36 | 914 |
| panelboard | 208V | HCB | 203 | 356 | 305 | 25 | 100 | Shallow LV panelboard at 208V | 18 | 457 |
| panelboard | 208V_DEEP | HCB | 610 | 356 | 305 | 25 | 100 | Deep LV panelboard at 208V | 18 | 457 |