Arc Flash Parameters: panelboard

IEEE 1584-2018 arc flash calculation parameters by equipment class and voltage class. Includes electrode gap (mm), working distance (inches), enclosure dimensions, and electrode configuration for switchgear, MCC, panelboard, and cable junction equipment.

Electrical Engineeringequipment_class: panelboard3 rows
equipment classvoltage classelectrode configenclosure depth mm (mm)enclosure height mm (mm)enclosure width mm (mm)gap mm (mm)insulation level pct (%)notesworking distance in (in)working distance mm (mm)
panelboard15KVVCB50891476215210015kV distribution panelboard / metering panel; IEEE 1584-2018 lacks a dedicated MV panelboard class — MV switchgear parameters applied per standard guidance; enclosure dimensions AI-estimated from typical MV panel36914
panelboard208VHCB20335630525100Shallow LV panelboard at 208V18457
panelboard208V_DEEPHCB61035630525100Deep LV panelboard at 208V18457

This is a sample. Search the full arc flash parameters dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE