Arc Flash Parameters: cable_junction

IEEE 1584-2018 arc flash calculation parameters by equipment class and voltage class. Includes electrode gap (mm), working distance (inches), enclosure dimensions, and electrode configuration for switchgear, MCC, panelboard, and cable junction equipment.

Electrical Engineeringequipment_class: cable_junction3 rows
equipment classvoltage classelectrode configenclosure depth mm (mm)enclosure height mm (mm)enclosure width mm (mm)gap mm (mm)insulation level pct (%)notesworking distance in (in)working distance mm (mm)
cable_junction15KVVCB2033563052510015kV cable junction / termination cabinet18457
cable_junction208VHCB20335630513100208V cable junction / pull box / termination cabinet (shallow); IEEE 1584-2018 electrode gap for cable junctions is voltage-independent (13 mm)18457
cable_junction208V_DEEPHCB61035630513100208V cable junction deep-enclosure variant (depth > 203.2mm, large pull box); gap and WD unchanged; depth correction factor applies per IEEE 1584-2018 §4.518457