Arc Flash Parameters: mcc

IEEE 1584-2018 arc flash calculation parameters by equipment class and voltage class. Includes electrode gap (mm), working distance (inches), enclosure dimensions, and electrode configuration for switchgear, MCC, panelboard, and cable junction equipment.

Electrical Engineeringequipment_class: mcc3 rows
equipment classvoltage classelectrode configenclosure depth mm (mm)enclosure height mm (mm)enclosure width mm (mm)gap mm (mm)insulation level pct (%)notesworking distance in (in)working distance mm (mm)
mcc15KVVCB91491491415210015kV motor control center; open-type36914
mcc208VHCB61035630525100Low-voltage MCC at 208V; shallow/deep same working distance18457
mcc208V_DEEPHCB61035630525100Low-voltage MCC 208V deep-compartment (depth > 203.2mm); parameters identical to 480V deep MCC per IEEE 1584-2018 §4.5.318457