Ups Sizing Data: online double conversion

40 to 500

UPS (Uninterruptible Power Supply) system sizing data for critical power design — covers offline/standby, line-interactive, online double conversion, and rotary topologies from 0.5 kVA to 1000 kVA; includes efficiency at 100% and 50% load, transfer time, output voltage regulation, output THD, overload capability, battery type, runtime at full load, heat dissipation, weight, and noise level

Electrical Engineeringups topology: online double conversion10 rowsPage 2 of 3
ups topologypower rating kVATHD output pct (%)battery typeefficiency pct at 100 load (%)efficiency pct at 50 load (%)heat dissipation BTU per hr (BTU/hr)noise dBA (dBA)output voltage regulation pct (%)overload capability pct for 10min (%)power factor (dimensionless)power rating kW (kW)standardtransfer time ms (ms)typical runtime min at full load (min)ups idweight lb (lb)
online double conversion402VRLA sealed lead-acid96955,6595321250.936Eaton 9355 40kVA; Schneider Galaxy VS 40kVA; Vertiv Liebert EXM2 40; IEEE 1100-199908ODC 40KVA450
online double conversion502VRLA sealed lead-acid96957,0785411250.945Eaton 9355 50kVA; Schneider Galaxy VS 50kVA; Vertiv Liebert EXL 50; IEEE 1100-1999; NFPA 11108ODC 50KVA550
online double conversion602VRLA sealed lead-acid96958,4975411250.954Eaton 9355 60kVA; Schneider Galaxy VM 60kVA; Vertiv Liebert GXT5; IEEE 1100-1999; NFPA 9909ODC 60KVA680
online double conversion802VRLA sealed lead-acid96.595.511,3305511250.972Eaton 9395 80kVA; Schneider Galaxy VX 80kVA; Vertiv Liebert APM; IEEE 1100-199909ODC 80KVA900
online double conversion1002VRLA sealed lead-acid96.595.512,8165611250.990Eaton 9395 100kVA; Schneider Galaxy VX 100kVA; Vertiv Liebert EXS; IEEE 1100-1999; Uptime Institute Tier III010ODC 100KVA1,200
online double conversion1502VRLA sealed lead-acid96.595.518,9065711250.9135Eaton 9395 150kVA; Schneider Galaxy VX 150kVA; Vertiv Liebert NX; IEEE 1100-1999010ODC 150KVA1,700
online double conversion2002VRLA sealed lead-acid96.595.526,1675711250.9180Eaton 9395 200kVA; Schneider Galaxy VM 200kVA; Vertiv Liebert NXL; IEEE 1100-1999010ODC 200KVA2,200
online double conversion2502VRLA or Li-ion96.595.529,7365811100.9225Eaton 9395 250kVA; Schneider Galaxy VM 250kVA; Vertiv Liebert NXC; IEEE 1100-1999010ODC 250KVA2,700
online double conversion4002VRLA or Li-ion979637,7285911100.9360Eaton 9395P 400kVA; Schneider Galaxy VX 400kVA; Vertiv Liebert EXL S1; IEEE 1100-1999; TIA-942010ODC 400KVA4,000
online double conversion5002VRLA or Li-ion979647,1606011100.9450Eaton 9395P 500kVA; Schneider Galaxy VX 500kVA; Vertiv Liebert EXL S1 500; IEEE 1100-1999; TIA-942010ODC 500KVA5,000