Ups Sizing Data: online double conversion
40 to 500
UPS (Uninterruptible Power Supply) system sizing data for critical power design — covers offline/standby, line-interactive, online double conversion, and rotary topologies from 0.5 kVA to 1000 kVA; includes efficiency at 100% and 50% load, transfer time, output voltage regulation, output THD, overload capability, battery type, runtime at full load, heat dissipation, weight, and noise level
| ups topology | power rating kVA | THD output pct (%) | battery type | efficiency pct at 100 load (%) | efficiency pct at 50 load (%) | heat dissipation BTU per hr (BTU/hr) | noise dBA (dBA) | output voltage regulation pct (%) | overload capability pct for 10min (%) | power factor (dimensionless) | power rating kW (kW) | standard | transfer time ms (ms) | typical runtime min at full load (min) | ups id | weight lb (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| online double conversion | 40 | 2 | VRLA sealed lead-acid | 96 | 95 | 5,659 | 53 | 2 | 125 | 0.9 | 36 | Eaton 9355 40kVA; Schneider Galaxy VS 40kVA; Vertiv Liebert EXM2 40; IEEE 1100-1999 | 0 | 8 | ODC 40KVA | 450 |
| online double conversion | 50 | 2 | VRLA sealed lead-acid | 96 | 95 | 7,078 | 54 | 1 | 125 | 0.9 | 45 | Eaton 9355 50kVA; Schneider Galaxy VS 50kVA; Vertiv Liebert EXL 50; IEEE 1100-1999; NFPA 111 | 0 | 8 | ODC 50KVA | 550 |
| online double conversion | 60 | 2 | VRLA sealed lead-acid | 96 | 95 | 8,497 | 54 | 1 | 125 | 0.9 | 54 | Eaton 9355 60kVA; Schneider Galaxy VM 60kVA; Vertiv Liebert GXT5; IEEE 1100-1999; NFPA 99 | 0 | 9 | ODC 60KVA | 680 |
| online double conversion | 80 | 2 | VRLA sealed lead-acid | 96.5 | 95.5 | 11,330 | 55 | 1 | 125 | 0.9 | 72 | Eaton 9395 80kVA; Schneider Galaxy VX 80kVA; Vertiv Liebert APM; IEEE 1100-1999 | 0 | 9 | ODC 80KVA | 900 |
| online double conversion | 100 | 2 | VRLA sealed lead-acid | 96.5 | 95.5 | 12,816 | 56 | 1 | 125 | 0.9 | 90 | Eaton 9395 100kVA; Schneider Galaxy VX 100kVA; Vertiv Liebert EXS; IEEE 1100-1999; Uptime Institute Tier III | 0 | 10 | ODC 100KVA | 1,200 |
| online double conversion | 150 | 2 | VRLA sealed lead-acid | 96.5 | 95.5 | 18,906 | 57 | 1 | 125 | 0.9 | 135 | Eaton 9395 150kVA; Schneider Galaxy VX 150kVA; Vertiv Liebert NX; IEEE 1100-1999 | 0 | 10 | ODC 150KVA | 1,700 |
| online double conversion | 200 | 2 | VRLA sealed lead-acid | 96.5 | 95.5 | 26,167 | 57 | 1 | 125 | 0.9 | 180 | Eaton 9395 200kVA; Schneider Galaxy VM 200kVA; Vertiv Liebert NXL; IEEE 1100-1999 | 0 | 10 | ODC 200KVA | 2,200 |
| online double conversion | 250 | 2 | VRLA or Li-ion | 96.5 | 95.5 | 29,736 | 58 | 1 | 110 | 0.9 | 225 | Eaton 9395 250kVA; Schneider Galaxy VM 250kVA; Vertiv Liebert NXC; IEEE 1100-1999 | 0 | 10 | ODC 250KVA | 2,700 |
| online double conversion | 400 | 2 | VRLA or Li-ion | 97 | 96 | 37,728 | 59 | 1 | 110 | 0.9 | 360 | Eaton 9395P 400kVA; Schneider Galaxy VX 400kVA; Vertiv Liebert EXL S1; IEEE 1100-1999; TIA-942 | 0 | 10 | ODC 400KVA | 4,000 |
| online double conversion | 500 | 2 | VRLA or Li-ion | 97 | 96 | 47,160 | 60 | 1 | 110 | 0.9 | 450 | Eaton 9395P 500kVA; Schneider Galaxy VX 500kVA; Vertiv Liebert EXL S1 500; IEEE 1100-1999; TIA-942 | 0 | 10 | ODC 500KVA | 5,000 |