Ups Sizing Data: online_double_conversion
UPS (Uninterruptible Power Supply) system sizing data for critical power design — covers offline/standby, line-interactive, online double conversion, and rotary topologies from 0.5 kVA to 1000 kVA; includes efficiency at 100% and 50% load, transfer time, output voltage regulation, output THD, overload capability, battery type, runtime at full load, heat dissipation, weight, and noise level
| ups topology | power rating kVA | THD output pct (%) | battery type | efficiency pct at 100 load (%) | efficiency pct at 50 load (%) | heat dissipation BTU per hr (BTU/hr) | noise dBA (dBA) | notes | output voltage regulation pct (%) | overload capability pct for 10min (%) | power factor (dimensionless) | power rating kW (kW) | transfer time ms (ms) | typical runtime min at full load (min) | ups id | weight lb (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| online_double_conversion | 1 | 2 | VRLA sealed lead-acid | 94 | 93 | 204 | 44 | True online double conversion; rectifier+inverter always active; zero transfer time; complete power conditioning; suitable for any critical load; higher heat loss at small sizes; ECO mode available on some models for improved efficiency | 2 | 125 | 0.9 | 0.9 | 0 | 6 | ODC_1KVA | 22 |
| online_double_conversion | 2 | 2 | VRLA sealed lead-acid | 94 | 93 | 409 | 45 | Online double conversion; constant power conditioning; IGBT rectifier; DSP-controlled sine wave inverter; static bypass; suitable for medical imaging servers telecommunications | 2 | 125 | 0.9 | 1.8 | 0 | 6 | ODC_2KVA | 35 |
| online_double_conversion | 3 | 2 | VRLA sealed lead-acid | 94 | 93.5 | 614 | 45 | Online double conversion; 3 kVA single-phase; commonly rack-mount 2U; HF transformer-less design; input PF correction; suitable for server rooms medical equipment | 2 | 125 | 0.9 | 2.7 | 0 | 6 | ODC_3KVA | 50 |