Rack Infrastructure Specs: OCP BBU Shelf

bbu shelf output voltage steady state min to bbu shelf startup time max

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP BBU Shelf4 rowsPage 3 of 3
component typespec parameterparameter nametest conditionunitvalue
OCP BBU Shelfbbu shelf output voltage steady state minBBU shelf steady state output voltage minimumSteady state; total regulation rangeV47.0
OCP BBU Shelfbbu shelf pkg dropPackaging drop test requirementISTA 3E 06-06in8
OCP BBU Shelfbbu shelf pkg vibrationPackaging vibration test requirement2-200-2 Hz; all three axes; random vibration per ISTA 3EGrms1.146
OCP BBU Shelfbbu shelf startup time maxBBU shelf startup time from activation to full rampIncluding peak load condition 150%ms2