Rack Infrastructure Specs: OCP BBU Shelf

bbu shelf output power max to bbu shelf output voltage steady state max

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP BBU Shelf8 rowsPage 2 of 3
component typespec parameterparameter nametest conditionunitvalue
OCP BBU Shelfbbu shelf output power maxBBU shelf output power maximum (6 modules)Rated; see module spec for peak load detailskW18
OCP BBU Shelfbbu shelf output power peakBBU shelf output power peak (6 modules)Peak; see module spec for detailskW27
OCP BBU Shelfbbu shelf output ripple voltage maxBBU shelf output ripple voltage maximumPeak to peakmVpp300
OCP BBU Shelfbbu shelf output voltage 100pct loadBBU shelf output voltage at 100% loadNominalV47.5
OCP BBU Shelfbbu shelf output voltage 150pct loadBBU shelf output voltage at 150% loadNominalV47.25
OCP BBU Shelfbbu shelf output voltage 50pct loadBBU shelf output voltage at 50% loadNominal setpointV47.75
OCP BBU Shelfbbu shelf output voltage boost limit sohBBU shelf output voltage boost limit for SOHBoost up to discharge energy at CP mode (e.g. 1.5 kW)V51.5
OCP BBU Shelfbbu shelf output voltage steady state maxBBU shelf steady state output voltage maximumSteady state; total regulation rangeV48.1