Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 19 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM50.0 1010.115070.2060.007674100.9267ASHRAE Fundamentals 2017 Ch.124.28
STD ATM50.0 10049.9850274.2310.0863271001.0425ASHRAE Fundamentals 2017 Ch.150.22
STD ATM50.0 2020.925090.610.01554200.9383ASHRAE Fundamentals 2017 Ch.129.51
STD ATM50.0 3027.6950111.530.023605300.9502ASHRAE Fundamentals 2017 Ch.133.47
STD ATM50.0 4032.750132.9860.031876400.9624ASHRAE Fundamentals 2017 Ch.136.71
STD ATM50.0 5036.72501550.040362500.9749ASHRAE Fundamentals 2017 Ch.139.49
STD ATM50.0 6040.0950177.5920.049072600.9877ASHRAE Fundamentals 2017 Ch.141.97
STD ATM50.0 704350200.7860.058013701.0008ASHRAE Fundamentals 2017 Ch.144.23
STD ATM50.0 8045.5850224.6060.067196801.0143ASHRAE Fundamentals 2017 Ch.146.33
STD ATM50.0 9047.8950249.0790.07663901.0282ASHRAE Fundamentals 2017 Ch.148.32

What else is in Engineering Database