Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 18 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM5.0 10-24.1756.3760.000536100.7886ASHRAE Fundamentals 2017 Ch.1-1.72
STD ATM5.0 1005.02518.590.0054021000.7948ASHRAE Fundamentals 2017 Ch.14.9
STD ATM5.0 20-16.1357.7230.001073200.7893ASHRAE Fundamentals 2017 Ch.1-1.12
STD ATM5.0 30-11.1559.0740.001611300.79ASHRAE Fundamentals 2017 Ch.1-0.51
STD ATM5.0 40-7.48510.4260.00215400.7907ASHRAE Fundamentals 2017 Ch.10.12
STD ATM5.0 50-4.56511.7810.002689500.7914ASHRAE Fundamentals 2017 Ch.10.8
STD ATM5.0 60-2.11513.1380.00323600.7921ASHRAE Fundamentals 2017 Ch.11.53
STD ATM5.0 700514.4980.003772700.7927ASHRAE Fundamentals 2017 Ch.12.31
STD ATM5.0 801.85515.860.004314800.7934ASHRAE Fundamentals 2017 Ch.13.13
STD ATM5.0 903.51517.2240.004858900.7941ASHRAE Fundamentals 2017 Ch.13.99